270
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Code
Name
Causes
Possible Solutions
E5
MECHATROLINK Watchdog
Timer Err
The drive detected a watchdog circuit exception
while it received data from the controller.
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
•
MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
•
MECHATROLINK-III Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP018)
Note:
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the stop method set in
F6-25 [MLII Watchdog Error Sel]
.
Code
Name
Causes
Possible Solutions
EF0
Option Card External Fault
The communication option card received an
external fault from the controller.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input from the controller.
A programming error occurred on the controller
side.
Examine the operation of the controller program.
Note:
•
The drive detects this fault if the alarm function on the external device side is operating.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the stop method set in
F6-03 [Comm Ext Flt Select (EF0)]
.
Code
Name
Causes
Possible Solutions
EF1
External Fault (Terminal DI1)
MFDI terminal DI1 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI1.
External Fault [H1-01 = 20 to 2B]
is set to MFDI
terminal DI1, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF2
External Fault (Terminal DI2)
MFDI terminal DI2 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI2.
External Fault [H1-02 = 20 to 2B]
is set to MFDI
terminal DI2, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF3
External Fault (Terminal DI3)
MFDI terminal DI3 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI3.
External Fault [H1-03 = 20 to 2B]
is set to MFDI
terminal DI3, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF4
External Fault (Terminal DI4)
MFDI terminal DI4 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI4.
External Fault [H1-04 = 20 to 2B]
is set to MFDI
terminal DI4, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
EF5
External Fault (Terminal DI5)
MFDI terminal DI5 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI5.
External Fault [H1-05 = 20 to 2B]
is set to MFDI
terminal DI5, but the terminal is not in use.
Correctly set the MFDI.
Note:
Do a Fault Reset to clear the fault.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...