Set the
x-xx
part of the
U: MONITORS
. For example, set
H4-01
to
102
to monitor
U1-02 [Output Frequency]
.
Note:
•
The configurable monitor changes when the control method changes.
•
To use in through mode, set this parameter to
000
or
031
. You can set the terminal AO1 output level from the PLC through Modbus
communications or the communication option.
■
H4-02 AO1 An.Out Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-02
(041E)
RUN
AO1 An.Out Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AO1.
100.0%
(-999.9 - +999.9%)
The analog signal output from the AO1 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-07 [AO1 Signal Level Select]
.
■
H4-03 AO1 An.Out Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-03
(041F)
RUN
AO1 An.Out Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AO1.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AO1 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-07 [AO1 Signal Level Select]
.
■
H4-04 AO2 An.Out Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-04
(0420)
AO2 An.Out Select
Sets the monitoring number to be output from the MFAO terminal AO2.
103
(000 - 999)
Set the
x-xx
part of the
U: MONITORS
. For example, set
H4-04
to
102
to monitor
U1-02 [Output Frequency]
.
Note:
•
The configurable monitor changes when the control method changes.
•
To use in through mode, set this parameter to
000
or
031
. You can set the terminal AO2 output level from the PLC through Modbus
communications or the communication option.
■
H4-05 AO2 An.Out Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-05
(0421)
RUN
AO2 An.Out Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AO2.
50.0%
(-999.9 - +999.9%)
The analog signal output from the AO2 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [AO2 Signal Level Select]
.
Examples of possible settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AO2
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AO2 terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
•
H4-04 = 103 [AO2 An.Out Select = Output Current]
•
H4-05 = 50.0%
•
H4-06 = 0.0% [AO2 An.Out Bias = 0.0%]
•
H4-08 = 0 [0 to 10 V]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...