SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
565
Configuration Parameter
Description
b5-90 [EZsleep Unit]
Sets the unit of measure for
b5-92 [EZsleep Level]
. When
b5-90 = 1[0.1Hz units]
, the setting range of
b5-91
[EZsleep Min Spd]
is 0.0 to 590.0 Hz. When
b5-90 = 0 [rpm]
, the setting range is 0 to 35400 min
-1
(r/min).
Note:
When you change
b5-90
, the value of
b5-92
is not automatically updated.
b5-91 [EZsleep Min Spd]
This parameter sets the lower limit for PID output. The drive uses the largest value of
b5-91
,
b5-34 [PID Out
Low Limit Level]
, and
d2-02 [FRef Lower Limit]
to internally set the lower limit of PID output. The
b5-89
setting does not have an effect.
b5-92 [EZsleep Level]
When the output frequency or motor speed is less than the value of
b5-92
for longer than the value of
b5-93
[EZsleep Time]
, the drive does to sleep.
b5-95 = 1 [EZsleep Wake Mode = Absolute]
When the PID feedback is less than the value of
b5-94 [EZsleep Wake Level]
for longer than the time set in
b5-96 [EZsleep Wake Time]
, the drive restarts operation from sleep.
b5-95 = 0 [EZsleep Wake Mode = Setpoint Delta]
When the PID feedback is less than the value set as the PID setpoint value minus
b5-94
for the time set in
b5-96
, the drive restarts operation from sleep.
Figure 12.32 EZ Sleep/Wake-up Operation: PID Output is Normal and b5-92 = 0.0 Hz
*1
The values of
b5-94
and
b5-95
set operation.
*2
In the example,
b5-92
is at the default setting of 0.0 Hz.
b5-91
is the EZ sleep level.
■
b5-01 PID Enable
No.
(Hex.)
Name
Description
Default
(Range)
b5-01
(01A5)
PID Enable
Enables PID control.
0
(0,1)
0 : Disabled
1 : Enabled
The drive does D control on the difference between the feedback value and the PID setpoint output through
U5-02
[PID Input]
.
■
b5-70 PID MainRefMode
No.
(Hex.)
Name
Description
Default
(Range)
b5-70
(01E5)
PID MainRefMode
Sets the PID main reference mode.
0
(0, 1)
0 : PID only
The drive does D control on the difference between the feedback value and the PID setpoint output through
U5-02
[PID Input]
.
1 : Fref + PID
The drive adds the frequency reference to the PID output. The drive does D control on the feedback output
through
U5-06 [PID AdjustFeedback]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...