556
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
■
b3-24 SpSrch Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
b3-24
(01C0)
SpSrch Method Selection
Sets the Speed Search method when starting the motor or when restoring power after a
momentary power loss.
2
(1, 2)
Set
b3-01 = 1 [SpSrch@Start Selection = Enabled]
to do Speed Search at start. Set
L2-01 = 1
[RideThru@PwrLoss = Enabled]
] to do Speed Search after you restore power after a momentary power loss.
1 : Speed Estimation
The drive uses the residual voltage from a short baseblock time to estimate the motor speed.
If there is not sufficient residual voltage, then the drive will inject DC current into the motor to estimate the motor
speed.
2 : Current Det2
The drive will inject DC current into the motor to estimate motor speed.
■
b3-25 SpSrch Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-25
(01C8)
Expert
SpSrch Wait Time
Sets the length of time the drive will wait to start the Speed Search Retry function.
0.5 s
(0.0 - 30.0 s)
If the drive detects these faults during speed search, increase the setting value:
•
oC [Overcurrent]
•
ov [Overvoltage]
•
SEr [Speed Search Retries Exceeded]
■
b3-26 Dir. Determ. Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-26
(01C7)
Expert
Dir. Determ. Level
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
1000
(40 - 60000)
■
b3-27 SS@RUNbeforeBB
No.
(Hex.)
Name
Description
Default
(Range)
b3-27
(01C9)
Expert
SS@RUNbeforeBB
Sets the conditions necessary to start Speed Search.
0
(0, 1)
Executes
Speed Search from Fmax or Fref [H1-xx = 67/68]
for initial speed searches or from the MFDI terminal.
0 : SS@RUNbeforeBB
1 : SS Always
■
b3-29 SpSrch BackEMF Threshold
No.
(Hex.)
Name
Description
Default
(Range)
b3-29
(077C)
Expert
SpSrch BackEMF
Threshold
Sets the induced voltage for motors that use Speed Search. The drive will start Speed Search
when the motor induced voltage level is the same as the setting value. Usually it is not necessary
to change this setting.
10%
(0 - 10%)
To make adjustments, gradually decrease the setting value. If you decrease the setting value too much, speed
search will not operate correctly.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...