SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
375
10.5
Drive Derating
You must derate the drive capacity to operate the drive above the rated temperature, altitude, and default carrier
frequency.
◆
Carrier Frequency Settings and Rated Current Values
The following tables show how the drive rated output current changes when
C6-02 [Carrier Frequency Selection]
value changes. The output current value changes linearly as the carrier frequency changes. You can use the values
from the tables to calculate a frequency that is not shown.
■
200 V Class
Table 10.13 Carrier Frequency and Rated Current Derating
Model
Rated Current (A)
Heavy Duty Rating (HD1)
Normal Duty Rating (ND1)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2004
3.2
3.2
3.2
3.1
2.9
2.78
3.5
3.3
2.9
2.7
2.4
2.10
2006
5.0
5.0
5.0
4.8
4.6
4.3
6
5.6
5
4.6
4.1
3.6
2010
8.0
8.0
8.0
7.4
6.6
5.8
9.6
9.0
8
7.4
6.6
5.8
2012
11.0
11.0
11.0
10.4
9.6
8.8
12
11.7
11
10.5
9.9
9.3
2018
14.0
14.0
14.0
12.6
10.8
9.1
17.5
16.1
14
12.6
10.8
9.1
2021
17.5
17.5
17.5
16.1
14.3
12.6
21
19.6
17
16.1
14.3
12.5
2030
25.0
25.0
25.0
23.0
20.5
18.0
30
28.0
25
23.0
20.5
18.0
2042
33.0
33.0
33.0
29.3
24.8
20.2
42
38.4
33
29.4
24.9
20.4
2056
47.0
47.0
47.0
43.4
38.9
34.4
56
52.4
47
43.4
38.9
34.4
2070
60.0
60.0
60.0
56.0
51.0
46
70
66.0
60
56.0
51.0
46.0
2082
75.0
75.0
75.0
68.6
60.5
53
82
82.0
75
68.8
61.0
53.1
2110
88.0
88.0
88.0
80.5
71.0
62
110
102.7
92
84.3
75.2
66.0
2138
115.0
115.0
115.0
105.1
92.8
81
138
128.8
115
105.8
94.3
82.8
2169
145.0
145.0
125.2
112.0
-
-
169
152.7
128.3
112.0
-
-
2211
180.0
180.0
155.2
138.6
-
-
211
190.2
158.9
138.1
-
-
2257
215.0
215.0
184.8
164.7
-
-
257
230.4
190.5
163.9
-
-
2313
283.0
283.0
249.0
226.4
-
-
313
288.5
251.7
227.1
-
-
2360
346.0
346.0
294.3
259.8
-
-
360
330.8
287.6
258.8
-
-
2415
415.0
415.0
365.2
332.0
-
-
-
-
-
-
-
-
■
400 V Class
Table 10.14 Carrier Frequency and Rated Current Derating (< 460 V)
Model
Rated Current (A)
Heavy Duty Rating (HD1)
Normal Duty Rating (ND1)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
4002
1.8
1.8
1.8
1.6
1.3
1.0
2.1
2.0
1.8
1.7
1.5
1.4
4004
3.4
3.4
3.4
2.9
2.3
1.7
4.1
3.8
3.4
3.1
2.8
2.4
4005
4.8
4.8
4.8
4.3
3.7
3.0
5.4
5.2
4.8
4.6
4.3
3.9
4007
5.5
5.5
5.5
4.9
4.1
3.2
7.1
6.5
5.5
4.8
4.0
3.2
4009
7.2
7.2
7.2
6.5
5.6
4.8
8.9
8.2
7.2
6.5
5.6
4.8
4012
9.2
9.2
9.2
8.1
6.8
5.4
11.9
10.8
9.2
8.1
6.7
5.4
4018
14.8
14.8
14.8
13.1
11.0
8.9
17.5
17.3
14.8
13.1
11.0
8.9
4023
18.0
18.0
18.0
15.9
13.4
10.8
23
21.5
18.3
16.2
13.6
11.0
4031
24.0
24.0
24.0
21.2
17.7
14.1
31
28.2
24.0
21.1
17.6
14.1
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...