
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
621
When the frequency reference or PID output value is 0% to 50%, the drive reverses the motor in the set direction.
When the frequency reference or PID output value is 50% to 100%, the drive operates the motor in the set
direction.
Note:
When you use the Bi-Directional function with PID control, you can use an MFDI terminal set for
PID BiDir [H1-xx = 7A]
to enable/
disable the Bi-Directional function.
shows how the drive operates when you use the PID control function with the Bi-Directional function
and
d4-11 = 1
:
Table 12.23 Bi-Directional Function Operation Conditions
b5-01 [PID Enable] Setting
Status of MFDI Terminal Set for 7F [PID Bi-Directional Enable]
ON
OFF
b5-01 = 0 [Disabled]
Bi-Directional function enabled
Bi-Directional function enabled
b5-01 ≠ 0 [Enabled]
Bi-Directional function enabled
Normal operation (Bi-Directional function disables)
•
When PID Control is Disabled or
H1-xx = 6A [DI Function Select = PID Disable]
is Activated
When the frequency reference is 0% to 50%, the drive reverses the motor in the set direction. When the
frequency reference is 50% to 100%, the drive operates the motor in the set direction.
shows the
frequency reference change at this time. This is an example of operation when the Forward Run command is
input.
Figure 12.62 Frequency Reference Transition when PID Control is Disabled or PID Disable is ON
Note:
When
b1-04 = 1 [Reverse Operation Selection = Disabled]
, the drive will not run in Reverse. The frequency reference limit is 0 Hz.
•
When PID Control is Enabled and
H1-xx = 7A [PID BiDir]
is Activated
The Bi-Directional function is enabled. When the frequency reference is 0% to 50% after PID control execution,
the drive runs the motor opposite of the set direction. When the frequency reference is 50% to 100%, the drive
runs the motor in the set direction.
shows the frequency reference change at this time. This is an
example of the operation when the Forward Run command is input.
Figure 12.63 Frequency Reference Transition when PID Control and PID Bi-Directional are Enabled
Note:
When
b1-04 = 1
, the drive will not run the motor in Reverse. The frequency reference limit is 0 Hz.
•
When PID Control is Enabled and
H1-xx = 7A
is Deactivated
The Bi-Directional function is disabled. When the frequency reference is a negative value after PID control
execution, the drive runs the motor opposite of the set direction. The frequency reference value is an absolute
value.
■
d4-12 Stop Position Gain
No.
(Hex.)
Name
Description
Default
(Range)
d4-12
(02B8)
Stop Position Gain
Sets the gain to adjust the stopping accuracy. Set this parameter when
b1-03 = 9 [Stopping
Method Selection = Distance Stop]
.
1.00
(0.50 - 2.55)
If the motor stops before the necessary stop position, increase the setting value. If the length of time for the motor
to stop is too long, decrease the setting value.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...