SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Byte
Command Message
Response Message
Response Message
Setting Data
(Hex.)
(when Normal)
Setting Data
(Hex.)
(when There is a Fault)
Setting Data
(Hex.)
8
Holding register
1 No.
Upper
00
-
-
9
Lower
02
-
-
10
Holding register
1 data
Upper
17
-
-
11
Lower
70
-
-
12
Holding register
2 No.
Upper
00
-
-
13
Lower
04
-
-
14
Holding register
2 data
Upper
05
-
-
15
Lower
DC
-
-
16
CRC-16
Upper
55
-
-
17
Lower
59
-
-
Note:
The number of bytes set within the command message determines the data quantity × 2 during the command message. The response
message uses the same formula.
◆
Enter Command
When you use Modbus communications to write parameters from the PLC to the drive, the
Mbus ENTER
Command Mode
setting sets the function to enable these parameters from the Enter command. This section gives
information about the Enter command.
■
Types of Enter Commands
The drive supports the two Enter commands shown in the following table.
Table 6.9 Types of Enter Commands
Register No.
(Hex.)
Description
0900
When you write parameter data to the EEPROM, you will enable the data on the RAM at the same time.
This process saves the parameter changes until you de-energize the drive.
0910
This updates the data on the RAM, but does not write data to the EEPROM.
This process saves the parameter changes until you de-energize the drive.
Write 0 to register number 0900 or 0910 (Hex.) to enable the Enter command. You can only write to these
registers. If you read to these registers, it will cause an error.
Note:
•
You can write the EEPROM to the drive a maximum of 100,000 times. Do not frequently execute the Enter command (0900 (Hex.))
that is written to EEPROM. The Enter command register is write-only. If this register is read, it will cause a Register Number Error (02
(Hex.)).
•
When the command data or broadcast message is transmitted to the drive, the Enter command is not necessary.
◆
Self-Diagnostics
The drive can use Self-Diagnostics to find the operation of the serial communications interface circuit. Self-
Diagnostics connects the transmission terminal to the reception terminal on the control circuit. It then transmits
the data sent by the drive and makes sure that the drive can communicate correctly.
Use this procedure to do Self-Diagnostics:
1.
Energize the drive.
2.
Set
H1-06 = 7F [DI6 Function Selection = Comms Test]
.
3.
De-energize the drive.
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...