770
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
■
L2-03 Min Baseblck Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-03
(0487)
Min Baseblck Time
Sets the minimum baseblock time when the drive restores power after a momentary power loss.
Determined by o2-04 and
C6-01
(0.1 - 5.0 s)
Sets the length of time that the drive will wait for the residual voltage in the motor to dissipate in estimation to the
secondary circuit time constant of the motor. If
oC [Overcurrent]
or
ov [DC Bus Overvoltage]
occur at the start of
Speed Search, after a power loss, or during DC Injection Braking, increase this setting.
■
L2-04 Powloss Ramp Time@recovery
No.
(Hex.)
Name
Description
Default
(Range)
L2-04
(0488)
Powloss Ramp
Time@recovery
Sets the time for the drive output voltage to go back to correct voltage after completing speed
searches.
Determined by o2-04 and
C6-01
(0.0 - 5.0 s)
Sets the time for voltage to recover from 0 V to the value set in
E1-05 [Max Output Voltage]
.
■
L2-05 UV Detection Lvl (Uv1)
No.
(Hex.)
Name
Description
Default
(Range)
L2-05
(0489)
UV Detection Lvl (Uv1)
Sets the voltage at which a
Uv1 [DC Bus Undervoltage]
fault is triggered or at which the KEB
function is activated. Usually it is not necessary to change this setting.
Determined by E1-01
(Determined by E1-01)
NOTICE:
Damage to Equipment. Install an AC reactor option on the input side of the power supply when setting this parameter
lower than the default value. Failure to obey will cause damage to drive circuitry.
Note:
If the low voltage detection level is near the lower limit value of
L2-05
, the drive will detect
Uv1
during KEB Ride-Thru operation. Do
not set the value too low when you use the KEB Ride-Thru function.
■
L2-06 KEB Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-06
(048A)
Expert
KEB Decel Time
Sets the deceleration time during KEB operation used to decrease the maximum output frequency
to 0.
0.0 s
(0.0 to 6000.0 s)
Set
L2-29 = 3 or 4 [KEB Method = System KEB1 Ride-Thru or System KEB2 Ride-Thru]
to enable this function.
When
L2-29 = 2, 3 , 4 [KEB Method = Single KEB2 Ride-Thru, System KEB1 Ride-Thru, System KEB2 Ride-
Thru]
and you do KEB Auto-Tuning, the drive will automatically set this value.
Sets the deceleration time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. If a
Uv1 [DC Bus Undervoltage]
fault occurs during KEB operation, decrease the
deceleration time. If an
ov [Overvoltage]
fault occurs, increase the deceleration time.
•
L2-06 = 0
The drive automatically decreases
C1-09 [Fast Stop Time]
to the base value to keep the DC bus voltage above
the low voltage detection level. The drive ignores
L2-02 [RideThrough Time@Power Loss]
in this condition.
•
L2-06 ≠ 0
As shown in
, the frequency reference decelerates to the KEB frequency level as specified by the
deceleration rate set in
L2-06
and then returns to the initial frequency reference as specified by
C1-01 [Accel
Time 1]
. The drive uses the setting value of the KEB frequency rate as shown in the this formula to set the KEB
frequency level:
KEB frequency level = Output frequency before power loss × (1 -
(L2-02)
/
(L2-06)
)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for Q2A
Page 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Page 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Page 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Page 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...