PCC-IV Instruction Manual (Rev. 0.1)
Page 6-17
Section 6
– Blockware Functions
Technical Reference
WARNING:
In a combustion application, it is not safe to leave the Learn Mode enabled during normal
operation. An accidental "Store" operation would instantly change the fuel/air ratio. The
Blockware should include sufficient logic and interlocks to prevent unsafe conditions.
The example below requires an external "Learn Enable" input to be a “1” (
DIN
Block 25), and both the fuel and air
must be in Manual before “Learn Mode” is enabled. A
DCON
could also be used as a permissive,
DCON
requires
a "Technician" level password to enable changing its Parameter.
WARNING:
This simplified example does not show all the required safety features that
would be included in a real combustion control strategy. Do not use the Blockware example
shown for an actual application.