PCC-IV Instruction Manual (Rev. 0.1)
Page 6-18
Section 6
– Blockware Functions
Technical Reference
---------------------------------------------------------------------------------------------
NAME: F(X) SINGLE USE FUNCTION: N OUTPUT TYPE: A
---------------------------------------------------------------------------------------------
Input Type Description Notes
_____________________________________________________________________________________________
1 A X INPUT
2 D LEARN ENABLE INPUT (1=ENABLE) 1
3 D LEARN INPUT (^1=LEARN) 2,3
4 D CLEAR INPUT (^1=CLEAR) 2,4
5 A Y INPUT 5
Parameter Description Default Max Min Code Notes
_____________________________________________________________________________________________
1 FIRST/LAST SEGMENT 0=HOLD
1=LINEAR 0 1 0 2
2 X1 0.00 150.00 -150.00 2 6
3 Y1 0.00 150.00 -150.00 2
4 X2 100.00 150.00 -150.00 2 6
5 Y2 100.00 150.00 -150.00 2
6 X3 -150.00 150.00 -150.00 2 6
7 Y3 50.00 150.00 -150.00 2
8 X4 -150.00 150.00 -150.00 2 6
9 Y4 50.00 150.00 -150.00 2
10 X5 -150.00 150.00 -150.00 2 6
11 Y5 50.00 150.00 -150.00 2
12 X6 -150.00 150.00 -150.00 2 6
13 Y6 50.00 150.00 -150.00 2
14 X7 -150.00 150.00 -150.00 2 6
15 Y7 50.00 150.00 -150.00 2
16 X8 -150.00 150.00 -150.00 2 6
17 Y8 50.00 150.00 -150.00 2
18 X9 -150.00 150.00 -150.00 2 6
19 Y9 50.00 150.00 -150.00 2
20 X10 -150.00 150.00 -150.00 2 6
21 Y10 50.00 150.00 -150.00 2
22 X11 -150.00 150.00 -150.00 2 6
23 Y11 50.00 150.00 -150.00 2
24 Y VALUE AFTER CLEAR 100.00 150.00 -150.00 2
Notes:
1. 1 = Learn Mode enabled, 0 = disabled.
2. This Input is ignored if LEARN ENABLE Input = 0.
3. The Learn Event is active during the single scan when the LEARN Input changes from 0 to 1,
AND (LEARN ENABLE Input equals 1 and CLEAR Input equals 0).
4. The Clear Event is active during the single scan when the LEARN Input changes from 0 to 1,
AND (LEARN ENABLE Input equals 1 and CLEAR Input equals 1).
5. The Y Input value is only used during the single scan of a Learn Event. The Input is limited
to +/- 150.00%.
6. The X coordinates MUST be in ascending order, that is: X1 < X2 < X3 < X4
… < X
11.
7. Xi = -150.00 indicates that the (X, Y) pair is inactive (i.e., not being used). All inactive
(X, Y
) pairs must be the “upper” X’s (i.e. X11, X10, X9, …)
. F(x) determines how many of
the eleven (X, Y) breakpoints to use by starting at X1, and scanning up looking for the
first Xi = -150.00. That pair and all pairs above it are ignored.