Parker EME
Technical Characteristics
192-120103 N13 C3I20T11 / C3I32T11 December 2010
405
Mains connection PSUP10D6
Device type PSUP10
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
22Arms
22Arms
18Arms
Output voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
6kW
10 kW
10 kW
Pulse power (<5s)
12kW
20kW
20kW
Power dissipation
60W
60W
60W
Maximum fuse rating per
device (=short circuit rating)
Measure for line and device protection:
MCB miniature circuit breaker (K characteristic) 25A in
accordance with UL category DIVQ
Recommendation: (ABB) S203UP-K 25(480VAC)
Mains connection PSUP20D6
Device type PSUP20
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
44Arms
44Arms
35Arms
Output voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
12kW
20kW
20kW
Pulse power (<5s)
24kW
40kW
40kW
Power dissipation
120W
120W
120W
Maximum fuse rating per
device (=short circuit rating)
2 circuit breakers in line are
required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D