Setting
up Compax3
C3I20T11 / C3I32T11
256
192-120103 N13 C3I20T11 / C3I32T11 December 2010
Open/Closed Loop frequency response measurement
In order to be able to analyze the transmission behavior of subordinate systems
(such as for example speed control, current control or mechanical system), the
influence of the superposed controls on the measurement must be avoided.
Influence of a superposed system on the frequency response measured
In the simplest case, the superposed controls are switched off completely (Open
Loop) This provides the best measurement results due to the elimination of any
influence caused by the superposed controls.
This is, however, rarely possible for reasons of safety or feasibility.
Caution!
Many systems are not stable without control!
Position as well as speed control are switched off
during measurement =>
no measurement on z-axes!
If you want to analyze for example the mechanic system of a z-axis, the position
control as well as the speed control must remain active.
In systems subject to friction it may be necessary in order to improve the quality of
the measurement, to
move the system with a superimposed speed
(see on
page 259), which is however only possible with a closed loop measurement.
Influence of an active superposed control on the result of the measurement
At the left without, at the right with the influence of the superposed control
In order to attenuate the influence of the superposed controls, the controller
bandwidth is reduced to such an extent, that their influence on the measurement is
negligible.