![Parker Compax3 C3I20T11 Operating Instructions Manual Download Page 43](http://html1.mh-extra.com/html/parker/compax3-c3i20t11/compax3-c3i20t11_operating-instructions-manual_3811584043.webp)
Parker EME
Compax3 device description
192-120103 N13 C3I20T11 / C3I32T11 December 2010
43
3.5.2.
Connections on the device bottom
Caution - Risk of Electric Shock!
Always switch devices off before wiring them!
Dangerous voltages are still present until 10 min. after switching off the power
supply.
Caution!
When the control voltage is missing there is no indication whether or not high
voltage supply is available.
Attention - PE connection!
PE connection with 10mm
2
via a grounding screw at the bottom of the device.
Attention - hot surface!
The heat dissipator can reach very high temperatures (>70°C)
P
Mains module PSUP
X40
Ballast resistor
X41
Mains supply VAC/PE
1
Central ground connection for the axis system,
with 10mm
2
to the ground screw on the housing.
4
Fan*
M
Axis controller
X43
Motor / Brake
2
Fixing for motor shield clamp
4
Fan*
3
optionally, the axis controller features a ground screw
on the housing, if the grounding is not possible via the
back plate.
* is internally supplied.
Line cross-sections of the power connections (on the device bottoms)
Compax3 device:
Cross-section: Minimum... Maximum [with conductor sleeve]
M050, M100, M150
0.25 ... 4 mm
2
(AWG: 23 ... 11)
M300
0.5 ... 6 mm
2
(AWG: 20 ... 10)
PSUP10
Mains supply: 0.5 ... 6 mm
2
(AWG: 20 ... 10)
Braking resistor: 0.25 ... 4 mm
2
(AWG: 23 ... 11)
PSUP20 & PSUP30
Mains supply: 0.5 ... 16 mm
2
(AWG: 20 ... 6)
Braking resistor: 0.25 ... 4 mm
2
(AWG: 23 ... 11)