Install a Fan Module
118
Sun Server X4-4 Service Manual • October 2015
also perform this procedure using cold service. Optional steps for partially extending the server
from the rack are included in this procedure.
Tip -
To view a video of replacing a fan module, see
http://docs.oracle.com/cd/E38212_01/
.
Before You Begin
■
For serviceability considerations, see
“Component Serviceability” on page 66
.
■
For fan module designation information, see
“Component Designations” on page 69
■
For instructions on removing a fan module, see
“Remove a Fan Module” on page 115
1.
If you are installing a replacement fan module for one that has failed, check the
indicator of the failed fan slot to ensure the fault indicator is no longer lit.
This is necessary to ensure the indicator status is cleared before you insert the new fan. See
“Fan Module Reference” on page 120
for fan module indicator locations.
2.
Orient the fan module so the connector on the bottom of the module is aligned
with the connector on the inside of the slot and all keying and labeling are
correctly positioned.
Summary of Contents for Sun Server X4-4
Page 1: ...Part No E38221 05 October 2015 Sun Server X4 4 Service Manual ...
Page 2: ......
Page 10: ...10 Sun Server X4 4 Service Manual October 2015 ...
Page 14: ...14 Sun Server X4 4 Service Manual October 2015 ...
Page 16: ...16 Sun Server X4 4 Service Manual October 2015 ...
Page 64: ...64 Sun Server X4 4 Service Manual October 2015 ...
Page 88: ...88 Sun Server X4 4 Service Manual October 2015 ...
Page 280: ...280 Sun Server X4 4 Service Manual October 2015 ...
Page 284: ...284 Sun Server X4 4 Service Manual October 2015 ...
Page 292: ...292 Sun Server X4 4 Service Manual October 2015 ...