Replace the Motherboard (FRU)
226
Sun Server X4-4 Service Manual • October 2015
25.
Install the air divider by aligning it with its guide and lowering it into the server.
Ensure that the flanges on the divider enter their respective slots on the side
wall and that the plunger for the Fault Remind button is aligned with the button
on the motherboard.
26.
Connect all cables from the power supply backplane, disk drive backplane, and
fan board to the motherboard.
27.
Install all memory risers.
See
“Install a Memory Riser Card” on page 138
28.
For a two-CPU system, install the air baffle, ensuring that the foot on the front of
the baffle is under the fan board ribbon cable.
29.
Install all PCIe cards.
See
“Install a PCIe Card” on page 151
.
30.
“Install the SP Card (FRU)” on page 217
.
31.
Install the power supply backplane cover plate.
Note -
Do not route the cables on the power supply backplane cover plate.
32.
Prepare the server for operation. See
.
Note -
The product serial number used for service entitlement and warranty coverage might
need to be reprogrammed by authorized service personnel with the correct product serial
number.
Summary of Contents for Sun Server X4-4
Page 1: ...Part No E38221 05 October 2015 Sun Server X4 4 Service Manual ...
Page 2: ......
Page 10: ...10 Sun Server X4 4 Service Manual October 2015 ...
Page 14: ...14 Sun Server X4 4 Service Manual October 2015 ...
Page 16: ...16 Sun Server X4 4 Service Manual October 2015 ...
Page 64: ...64 Sun Server X4 4 Service Manual October 2015 ...
Page 88: ...88 Sun Server X4 4 Service Manual October 2015 ...
Page 280: ...280 Sun Server X4 4 Service Manual October 2015 ...
Page 284: ...284 Sun Server X4 4 Service Manual October 2015 ...
Page 292: ...292 Sun Server X4 4 Service Manual October 2015 ...