84
SECTI
ON 4
De
fine
Z500
Operation Manual
SECTION 4
Menus for Expert Menu
#3
Set Output Conditions
Set the output conditions of measurement results as necessary
.
The asterisk (*) indicates the default setting.
Span and Offset
CHECK
When calibration is executed, the span and the offset will be automatically set.
Item
Selection
Description
Upper
-9999.99999 to
9999.99999
Set the judgment conditions. Set the range for a PASS
judgment.
Lower
Hold
Set when the Trigger function is used. Select the contents of the data to
be held.
REFERENCE
For details on the Trigger function, refer to page 90.
None*
Hold measurement is not performed.
Sampling
The value at the start of measurement is held.
Peak
The highest value measured during measurement is
held.
Bottom
The lowest value measured during measurement is held.
Peak-Peak
The difference between the highest and lowest values
measured during measurement is held.
Average
The average value between the highest and lowest
values measured during measurement is held.
Zero
-9999.99999 to
9999.99999
Set the offset value for force-zero execution.
Set the value to be added to 0.
REFERENCE
Refer to page 110,
Force-zero.
Span
0.20000 to
4.00000
(1.00000*)
Set to make fine adjustments to measurement values
after calibration. Set for the incline in the Sensor
characteristics.
Offset
-9999.99999 to
9999.99999
(0.00000*)
Set to make fine adjustments to measurement values
after calibration. Added to or subtracted from
measurement values that have been set.
Unit
mm*
mm
2
None
Select the unit of the measured values to be displayed on
the monitor screen.
Measurement value
(mm)
Displacement
of workpiece
0.2
4.0
A coefficient (the span) is set to compensate
for incline in the Sensor characteristics.
Span
Measurement value
(mm)
Displacement
of workpiece
Offset
A fixed value (the offset) is added to or
subtracted from measurement values.