217
Temperature Input Units
Section 6-4
11. Click the
Fix upper adjusting Value
Button. The upper limit adjustment
value will be stored in the Unit.
12. To check whether the user adjustment values have been accepted and the
Unit is operating with adjustment values different from the factory defaults,
click the right mouse button over the Slave icon and select
Maintenance
Information
to open the Maintenance Information Window.
Select the Tab Page for the input that was adjusted. If there is a check in
the
User Adjustment
Box (bottom right box), the Unit is operating with us-
er-set adjustment values.
Note
1.
When checking whether or not the user adjustment values have been set
correctly, always refresh the data by clicking the
Update
Button in the
Maintenance Information Window’s
General
Tab or uploading the settings
again. For details on the Maintenance Information Window, refer to
6-3
Maintenance Information Window
.
2.
If the correct reference voltage was not input, the adjustment values may
not be accepted.
■
Adjusting the GRT1-TS2T’s Bias Compensation Value
1,2,3...
1.
Remove the wiring for upper/lower limit compensation and wiring the Unit
as shown for bias compensation.
2.
After completing wiring, wait until the temperature data stabilizes (i.e., until
there is no change in the temperature data for at least 20 minutes). De-
pending on the system setup, this may take over 60 minutes. When the
temperature data is stable, click the
Fix Bias adjusting Value
Button.
N
50 mV
PL2
50 mV
Input type
Input voltage
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...