269
GRT1-CP1-L Positioning Unit
Section 7-5
■
Preset Value
Set the
Preset value
Field to the desired preset value. The set value will be
stored in the Preset Value Register.
The following figure shows how the preset value works. In this example, a
fixed frequency is input from the encoder to the counter and the preset value
is set to 1000.
The preset value can be set to between –2,147,483,648 (8000 0000 hex) and
2,147,483,647 (7FFF FFFF hex).
This setting is stored in non-volatile memory. If the setting is changed, the new
value is effective immediately.
■
Default Settings
Press the
Default Setting
Button on the
Preset
Tab Page to set the following
default value.
Range 0 and Range 1 Tab
Pages
A Positioning Unit supports two comparison ranges, one for each digital out-
put. The tab page to set a comparison range is displayed only when the range
is enabled. Click the
Range 0
or
Range 1
Button on the
Positioning
Tab Page
to enable using the range and display the
Range 0
or
Range 1
Tab Page. The
digital output will not be controlled by the comparison function unless the cor-
responding range is set.
The Range 0 Tab Page is used to describe the functionality in this manual, but
the functionality is the same for range 1.
Note
The digital output will be controlled by the corresponding range only when the
Output 0 Control Bits (bits 12 and 13 of word n+2) or Output 1 Control Bits
(bits 14 and 15 of word n+2) are OFF.
Counter preset
Preset value = 1000
Count
Time
Setting
Default value
Preset value
0
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...