Analog Input Units
Section 5-4
Setting Hysteresis
The Comparator Result Flag turns OFF when the value is lower than the hys-
teresis width (H or HH alarm occurs) or exceeds it (L or LL alarm occurs), as
shown in the following diagram. If the analog value fluctuates around the
threshold, and the flag repeatedly turns ON or OFF, setting hysteresis will sta-
bilize the flag operation.
OFF Delay
The time until the Comparator Result Flag turns OFF can be extended. For
example, even if the Flag is ON momentarily, the OFF delay can be set so that
the Master can receive notification of the Flag’s status.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1.
In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select
Parameters - Edit
. The Edit Device Parameters
Window will be displayed.
2.
Click the
I/O Module
Tab.
3.
Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
HH set value or
H set value
Hysteresis width
LL set value or L
set value
Hysteresis
width
HH Alarm Flag or
H Alarm Flag
LL Alarm Flag or
L Alarm Flag
HH set value
Hysteresis width
OFF delay
HH Alarm Flag
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...