200
Temperature Input Units
Section 6-4
4.
Select the Tab Page for the input where rate of change is to be set, and
select the
Rate of Change
Option in the
Function Choice
Area.
5.
To set the sampling cycle, click the
Rate of Change
Tab and input the de-
sired value for the sampling cycle in the
Sampling Rate
Field.
6.
Return to the
General
Tab, click the
Download
Button, and then click the
Reset
Button to reset the Unit.
7.
Click the
OK
Button and exit the window.
Comparator
When the High High Limit, High Limit, Low Low Limit, and Low Limit are set in
the Unit, a Status Flag will turn ON when a value exceeds a setting range. The
four set values are High High Limit (HH), High Limit (H), Low Low Limit (LL),
and Low Limit (L), and the values can be compared with those in Temperature
Data.
The setting range is from
−
415000 to 415000.
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...