150
Analog Output Units
Section 5-5
Adjusting the High Limit
10. Output the value from the Master Unit that is equivalent to the Output Unit’s
maximum (100%) value. Adjustment is best performed using the 100% val-
ue, but can be performed using a lower value.
11. Adjust the analog value that is output from the terminal using the High Limit
slide bar, as shown in the following window. Repeat adjustments until the
correct 100% value is output from the output device. After compensation is
completed, click the
Fix upper adjusting Value
Button.
Note
If the High Limit adjustment is not performed for the 100% value, a discrep-
ancy will occur when the Low Limit is adjusted, so always adjust the Low Limit
of Output Units before adjusting the High Limit.
Cumulative Counter
The cumulative counter calculates an approximation to the integral of analog
output values over time. The cumulated value can be calculated in “count
hours” (by selecting “hours”) or “count minutes” (by selecting “minutes”). The
count value is the analog output value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
output value of 100 counts continuing for one hour. The counter range for a
four-byte area (two words) for count hours or count minutes is –214,748,364.8
to 214,748,364.7. Data is displayed on the Configurator in units of 0.1 hours
or minutes.
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...