169
Temperature Input Units
Section 6-4
Note
The indication accuracy depends on the mounting direction and the Units on
both sides of and directly next to the GRT1-TS2T. Refer to the following infor-
mation.
■
Indication Accuracy Dependence on Mounting Direction and Mounted
Units
The indication accuracy depends on the direction in which the Temperature
Input Unit is mounted and on the Units mounted on both sides and directly
next to the GRT1-TS2T. The following indication accuracy applies if the stan-
dard mounting direction (i.e., mounting 1) is not used or if the Units mounted
are not on the list of Units supporting an indication accuracy of
±
2
°
C
±
1 digit
max.
±
4
°
C
±
1 digit max.
The following are exceptions.
Indication
accuracy
±
2
°
C
±
1 digit max. (See note.)
The following are exceptions.
Input type
Input accuracy
K, T, or N below
−
100
°
C
±
4
°
C
±
1 digit max.
U, L, or PL2
±
4
°
C
±
1 digit max.
R or S below 200
°
C
±
4
°
C
±
1 digit max.
B below 400
°
C
Not specified
W
±
6
°
C
±
1 digit max.
The indication accuracy applies under the following conditions.
• The standard mounting direction must be used (i.e., mounting 1).
• The terminal block and main block must have the same serial
number.
• The Units on both sides of and directly next to the GRT1-TS2T
must be in the following list of Units supporting an indication accu-
racy of
±
2
°
C
±
1 digit max.
Conversion
cycle
250 ms/2 points
Temperature
conversion data
Binary data two's complement (Four-digit hexadecimal when nor-
mal display mode is selected or 8-digit hexadecimal when 1/100
display mode is selected.)
Isolation method Between input and communications lines: Photocoupler isolation
Between temperature input signals: Photocoupler isolation
Items
Specifications
Input type
Input accuracy
K, T, or N below
−
100
°
C
±
7
°
C
±
1 digit max.
U, L, or PL2
±
7
°
C
±
1 digit max.
R or S below 200
°
C
±
7
°
C
±
1 digit max.
B below 400
°
C
Not specified.
W
±
9
°
C
±
1 digit max.
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...