Temperature Input Units
Section 6-4
occurs.) The comparator can be used to compare the top or valley value allo-
cated as temperature data. (Refer to details on the comparator function.)
■
Example of Valley Hold
Note
1.
A delay in network transmission time will occur from the time the Hold Flag
turns ON (or OFF) in the Master’s ladder program until notification of the
flag’s status is actually sent to the Slave. Therefore, even when the Hold
Flag is ON, the first temperature data transmitted to the Master when the
CPU Unit power is turned ON may be the data from when the Hold Flag
was OFF. To collect top/valley hold data using the Hold Flag at the Master,
configure a ladder program which considers the transmission delay time
when the Hold Flag is turned ON, then enables the top/valley hold values
after a fixed time interval.
2.
The time that the Top/Valley Detection Timing Flags are ON can be adjust-
ed by setting the one-shot time. Use the Configurator to set the one-shot
time (the setting range is 1 to 65535 ms).
3.
If the Hold Flag turns OFF during the time the Top/Valley Detection Timing
Flag is set to be ON, both flags will turn OFF simultaneously.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1.
In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select
Pa-
rameters - Edit
. The Edit Device Parameters Window will be displayed.
2.
Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3.
Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
Analog input value
Valley hold value
Last value is held.
Hold value
Hold Flag
Hold function starts
Hold function stops
Top/Valley Detection
Timing Flag
One-shot time
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...