190
Temperature Input Units
Section 6-4
upper limit is 7FFE hex and the lower limit is 8000 hex. (In 1/100 Display
Mode the upper limit is 7FFFFFFE hex and the lower limit is 80000000 hex.)
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1.
In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select
Pa-
rameters - Edit
. The Edit Device Parameters Window will be displayed.
2.
Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3.
Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4.
Select the tab page for the input where scaling is to be performed, and se-
lect the
Scaling
Check Box in the
Function Choice
Area.
Upper limit 7FFE
100% scaling value
Scaled line
0% scaling
Offset value
(–28,000 to
28,000)
Input signal range
0%
100%
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...