308
Explicit Messages
Appendix A
Setting and Monitoring Output Terminals
Explicit
message
Read/
write
Function Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode
Read
Reads the specified
output’s monitor
mode for mainte-
nance information.
0E hex
8E hex
01 to 40
hex
*1
85 hex
---
4 bytes
0: Total ON time
mode
1: Contact oper-
ation counter
mode
The mode is
read for out-
puts 0 to 32.
*10
Write
Writes the specified
output’s monitor
mode for mainte-
nance information.
10 hex
8E hex
01 to 40
hex
*1
85 hex
4 bytes
0: Total ON time
mode
1: Contact oper-
ation counter
mode
The mode is set
for outputs 0 to
32.
*10
Set all
other bits to 0.
---
Set Value of
Output
Mainte-
nance
Counter
Read
Reads the set value
for the total ON time
(unit: s) or number
of contact opera-
tions (unit: opera-
tions) the output (0
to 3, or 0 to 7 for an
Eight-output Unit)
specified by the
Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
78 hex
*2
7B hex
*3
7E hex
*4
81 hex
*5
A8 hex
*6
AB hex
*7
AE hex
*8
B1 hex
*9
---
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4294967295
decimal)
Write
Writes the set value
for the total ON time
(unit: s) or number
of contact opera-
tions (unit: opera-
tions) for the output
(0 to 3, or 0 to 7 for
an Eight-output
Unit) specified by
the Attribute ID.
10 hex
8E hex
01 to 40
hex
*1
78 hex
*2
7B hex
*3
7E hex
*4
81 hex
*5
A8 hex
*6
AB hex
*7
AE hex
*8
B1 hex
*9
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4294967295
decimal)
---
Read Out-
put Mainte-
nance
Counter
Read
Reads the total ON
time (unit: s) or
number of contact
operations (unit:
operations) for the
output (0 to 3, or 0
to 7 for an Eight-out-
put Unit) specified
by the Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
77 hex
*2
7A hex
*3
7D hex
*4
80 hex
*5
A7 hex
*6
AA hex
*7
AD hex
*8
B0 hex
*9
---
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4294967295
decimal)
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...