259
GRT1-CP1-L Positioning Unit
Section 7-5
Note
Each command is executed only once when the command bit is turned ON.
Command bits are not reset automatically and must be reset by the user.
Make sure to reset the command bit after execution of the command has been
completed (i.e., after the corresponding Completed Flag has turned ON in
word m+2). Also, make sure that all command bits are OFF when the Unit is
started, including when starting a new Unit after Unit replacement.
n+2
(contin-
ued)
04
Counter Data Display Command Bit (See note.)
Turn ON this bit to change the register displayed in the Counter Data (words m and m+1) to the
register specified by the Register Selection Bits (bits 00 to 02 of word n+2). The specified register
will not change regardless of write actions.
05
Digital Input Enable Bit
This bit enables and disables the digital input.
OFF: The function assigned to the digital input is disabled.
ON: The function assigned to the digital input is enabled.
06 and
07
Z Input Counter Reset Mode Bits
These bits set the counter reset mode for the Z input.
Bit: 07 06
0 0 = Z input is ignored
0 1 = The counter value is reset to zero on first rising edge of the Z input.
1 0 = The counter value is reset to zero on every rising edge of the Z input.
1 1 = The counter value is reset to zero on every rising edge of the Z input if the digital input
(IN) is ON.
08
Gate Control Bit
This bit enables and disables the counter.
OFF: Counting is enabled.
ON: Counting is disabled (i.e., no pulses are counted), and the Present Counter Value will not
change in response to encoder inputs.
The Present Counter Value can be changed using a reset or preset command even when counting
is disabled.
09
Capture Command Bit
(See note.)
Turn ON this bit to store the Present Counter Value in the Capture Value Register.
10
Preset Command Bit
(See note.)
Turn ON this bit to set the Preset Value Register to the Present Counter Value.
11
Reset Command Bit
(See note.)
Turn ON this bit to reset the Present Counter Value to 0.
12 and
13
Output 0 Control Bits
These bits control digital output 0 (OUT0).
Bit: 13 12
0 0 = Digital output 0 controlled by range 0 (LL0 and UL0).
0 1 = Digital output 0 turned OFF.
1 0 = Digital output 0 turned ON.
1 1 = Digital output 0 turned ON.
14 and
15
Output 1 Control Bits
These bits control digital output 1 (OUT1).
Bit: 15 14
0 0 = Digital output 1 controlled by range 1 (LL1 and UL1).
0 1 = Digital output 1 turned OFF.
1 0 = Digital output 1 turned ON.
1 1 = Digital output 1 turned ON.
Word
Bits
Definition
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...