304
Explicit Messages
Appendix A
Source Node Address
The node address of the node from which the command was sent is returned in hexadecimal.
Service Code
For normal completion, the value when the leftmost bit of the service code specified in the command turns ON
is stored as shown in the following table.
When an error response is returned for an explicit message, the value is always 94 hex.
Data
Read data is included only when a read command is executed.
Error Codes
The explicit message error code. For details, refer to the list of error codes in the following table.
List of Error Codes
Explicit Messages Shared by All Slice I/O Units
Reading Status
Note
The Instance ID specifies the Slice I/O Unit’s unit number (1 to 63 decimal).
Function
Command service code
Response service code
Write data
10 hex
90 hex
Read data
0E hex
8E hex
Reset
05 hex
85 hex
Save
16 hex
96 hex
Response code
Error name
Cause
08FF
Service not supported
The Service code is incorrect.
09FF
Invalid Attribute value
The specified Attribute value is not supported.
The data written was outside valid range.
16FF
Object does not exist
The specified Instance ID is not supported.
15FF
Too much data
The data is larger than the specified size.
13FF
Not enough data
The data is smaller than the specified size.
0CFF
Object state conflict
The specified command cannot be executed due to an internal error.
20FF
Invalid parameter
The specified operation command data is not supported.
0EFF
Attribute not settable
An Attribute ID supported only for reading has been executed for a
write service code.
10FF
Device state conflict
The specified command cannot be executed due to an internal error.
14FF
Attribute not supported
The specified Attribute is not supported.
19FF
Store operation failure
The data cannot be stored in memory.
2AFF
Group 2 only server general
failure
The specified command or Attribute is not supported or the Attribute
was not set.
Explicit
message
Read/write
Function Command
Response
Service
code
Class ID
Instance ID
Attribute
ID
Data size
Warning
Information
Read
Read
Reads the Slice
I/O Unit’s warn-
ing status data.
0E hex
8D hex
01 to 40 hex
(See note.)
72 hex
---
2 bytes
Alarm Infor-
mation
Read
Read
Reads the Slice
I/O Unit’s alarm
status data.
0E hex
8D hex
01 to 40 hex
(See note.)
73 hex
---
2 bytes
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...