123
Analog Input Units
Section 5-4
value. This will cause the start of data holding to be delayed after the actual
top or valley value occurs, as shown in the following diagram.
■
Timing for Setting Data
■
Setting Hysteresis (Example: DeviceNet Configurator)
1,2,3...
1.
Input the value for hysteresis in the
Hysteresis
Field in the
Top/Valley
Tab
in the
Function Choice
Area.
2.
Return to the
General
Tab Page, click the
Download
Button, and then click
the
Reset
Button to reset the Unit.
3.
Click the
OK
Button to exit.
Note
The hysteresis value set for the top/valley hold function is also used by the
comparator function.
Analog input value
Set hysteresis value
×
2
Valley hold value
Top/Valley Detection
Timing Flag
Delay
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...