222
Temperature Input Units
Section 6-4
Checking the Wiring and
Making Adjustments
■
Adjusting the Upper and Lower Limit Values
1,2,3...
1.
Set the resistance value on the six-dial resistance box equivalent to the
test value and properly wire the box to the input of the Temperature Input
Unit that is being adjusted.
2.
If the correct resistance cannot be obtained, properly wire the digital mul-
timeter to the six-dial resistance box and measure the resistance.
3.
Connect the Configurator to the DeviceNet network and go online.
4.
Upload settings to the Configurator.
5.
Turn ON the power supplies of all Units, including the Temperature Input
Unit to be adjusted. Wait approximately 30 minutes for the Temperature In-
put Unit’s internal temperature to stabilize.
6.
Double-click the icon of the Temperature Input Unit to be set in the window
to open the Edit Unit Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the icon and select
Parameters
- Edit.
)
7.
Select the tab page for the input that will be adjusted and click the
Adjust-
ment
Button to open the Adjustment Window.
8.
Adjust the lower limit value (lower adjusting value). Refer to the following
table for the appropriate resistance to input from the six-dial resistance box
to the Temperature Input Unit’s input terminals. Wait at least 1 minute for
the input to stabilize.
Model
Input type
Lower limit
adjustment input
resistance
GRT1-TS2P
PT100 (
−
200 to 850
°
C)
18
Ω
PT100 (
−
200 to 200
°
C)
18
Ω
GRT1-TS2PK
PT1000 (
−
200 to 850
°
C)
180
Ω
PT1000 (
−
200 to 200
°
C)
180
Ω
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...