224
Temperature Input Units
Section 6-4
13. To check whether the user adjustment values have been accepted and the
Unit is operating with adjustment values instead of the default values,
right-click device icon and select
Maintenance Information
to open the
Maintenance Information Window. Select the tab page for the input that
was adjusted. If the
User Adjustment
Check Box (bottom right box) is
selected, the Unit is operating with user-set adjustment values.
Note
(1) When checking whether or not the user adjustment values have been set
correctly, always refresh the data by clicking the
Update
Button on the
Maintenance Information Window’s
General
Tab Page or uploading the
settings again. For details on the Maintenance Information Window, refer
to
6-3 Maintenance Information Window
.
(2) Always test the display accuracy after making user adjustments to verify
that the adjustments are correct. Test the display accuracy at three
points: the lower limit value, an intermediate value, and the upper limit
value.
• Connect the external devices as shown in the following diagram.
• Wait at least 30 minutes after the Temperature Input Unit’s power is
turned ON and set the resistance value on the six-dial resistance box
equivalent to the test value.
Note
After adjustment, it is not necessary to wait 30 minutes if continuing
testing without turning the power OFF.
Input B
Input A
Six-dial resistance box
GRT1-TS2P or
GRT1-TS2PK
Input B
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...