173
Temperature Input Units
Section 6-4
■
GRT1-TS2P
■
GRT1-TS2PK
■
GRT1-TS2T
Note
1.
Use the Setting Tool to make the setting if an input type other than those
listed above will be used (GRT-TS2T only).
2.
Always set Pin 4 to ON if the DIP switch is to be used to set the input type.
If this pin is OFF, the DIP switch settings will not be enabled.
3.
The DIP switch settings are read when the power is turned ON.
4.
If pin 4 is set to ON, you will not be able to set any functions, including the
input type, from the Setting Tool. Always set pin 4 to OFF when using the
Setting Tool.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1.
In the Network Configuration Window for the Slice I/O Terminal, dou-
ble-click the icon of the Slice I/O Terminal that is to be set. Alternatively,
right-click the icon and select
Parameters - Edit
. The Edit Device Param-
eters Window will be displayed.
2.
Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3.
Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4.
Select the tab page for the input where the input type is to be changed.
SW1
SW2
Input type
OFF
OFF
PT100 (
−
200 to 850
°
C)
OFF
ON
PT100 (
−
200 to 200
°
C)
SW1
SW2
Input type
OFF
OFF
PT1000 (
−
200 to 850
°
C)
OFF
ON
PT1000 (
−
200 to 200
°
C)
SW1
SW2
Input type
OFF
OFF
R
ON
OFF
S
OFF
ON
K (
−
200 to 1,300
°
C)
ON
ON
J (
−
100 to 850
°
C)
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...