
213
Temperature Input Units
Section 6-4
Adjustment Procedure for
the GRT1-TS2T
Use the following procedure to adjust the Temperature Input Terminal. Follow
the flowchart closely for proper adjustment.
Note
The only sensors that can be adjusted are ones that operate while the power
supply is ON. When adjusting for sensors that are not presently in use,
change the input type setting, toggle the power supply or reset the Unit from
the Configurator, and perform the adjustment procedure from the beginning of
the flowchart.
No
Yes
No
Yes
Prepare the devices required for adjustment.
Connect the devices required for adjustment (i.e.,
upper/lower limit adjustment).
First
adjustment?
Turn ON the power to the related system
devices. Wait at least 30 minutes for the
GRT1-TS2T’s internal temperature to stabilize.
This stabilization time is the time required
when the power is turned ON for the first time.
This step can be skipped when adjusting the
second and following inputs.
Refer to the
Operating Manuals
for the other
devices in the system for details on their
required stabilization times, if any.
Set the input's lower limit adjustment value.
Set the input's upper limit adjustment value.
Remove the devices connected for upper/lower
limit adjustment and connect the devices
require for bias compensation. Wait 60 minutes
for the terminal block temperature to stabilize.
A cold junction compensator and compensating
conductor (e.g., zero conductor) are required
for the thermocouple being adjusted.
Set the input's bias compensation.
Adjust other
inputs?
Test indication accuracy after adjustment.
End
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...