
201
Temperature Input Units
Section 6-4
When any of these values is exceeded, the Comparator Result Flag in the
area for Temperature Status Flags turns ON. If an alarm does not occur, the
Normal Flag (pass signal) turns ON.
Note
If the temperature input value changes faster than the conversion cycle, the
High Limit alarm may turn ON without the Normal Flag (pass signal) turning
ON for the Low Limit alarm. Configure ladder programs to prevent this occur-
ring.
Setting Hysteresis
The Comparator Result Flag turns OFF when the value is lower than the hys-
teresis width (H or HH alarm occurs) or exceeds it (L or LL alarm occurs), as
shown in the following diagram. If the temperature value fluctuates around the
threshold, and the flag repeatedly turns ON or OFF, setting hysteresis will sta-
bilize the flag operation. The setting range is from 0 to 16383.
Note
When setting the hysteresis value, adjust for each input’s decimal point posi-
tion and the 1/100 Display Mode (if it is being used). Always correct the hys-
teresis value after changing the display mode setting or changing to an input
that has a different decimal point position.
OFF Delay
The time until the Comparator Result Flag turns OFF can be extended. For
example, even if the Flag is ON momentarily, the OFF delay can be set so that
the Master can receive notification of the Flag’s status.
Set values
HH
H
L
LL
Comparator Result Flag
(in Temperature Status
Flags) ON/OFF
HH alarm
H alarm
Normal Flag
(Pass signal)
L alarm
LL alarm
HH set value or
H set value
Hysteresis width
LL set value or L
set value
Hysteresis
width
HH Alarm Flag or
H Alarm Flag
LL Alarm Flag or
L Alarm Flag
HH set value
Hysteresis width
OFF delay
HH Alarm Flag
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...