253
GRT1-CP1-L Positioning Unit
Section 7-5
Encoder A, B, and Z
Inputs
24 V Inputs
Line Driver Inputs
Digital Input (IN)
Note
The response time is the time between the moment the A, B, Z, or IN input
turns ON or OFF and the moment the digital output is updated to the new
state. The specified response time may not be achieved during monitoring or
maintenance.
Digital Outputs
(OUT0 and OUT1)
Note
The response time is the time between the moment the A, B, Z or IN input
turns ON or OFF and the moment the digital output is updated to the new
state. The specified response time may not be achieved during monitoring or
maintenance.
Item
Specification
Input type
PNP
Number of inputs
3 (encoder inputs A, B, and Z)
ON voltage
18.6 VDC min. (between input terminal and G terminal)
ON current
3.0 mA min.
OFF voltage
4.0 VDC max. (between input terminal and G terminal)
OFF current
1.0 mA max.
Maximum input signal
frequency
60 kHz for pulse/direction counter mode
60 kHz for up/down counter mode
30 kHz for phase differential counter mode (
×
1,
×
2, or
×
4)
Item
Specification
ON voltage
2.0 VDC min. (RS-422 line driver-compatible level)
OFF voltage
0.8 VDC max. (RS-422 line driver-compatible level)
Number of inputs
3 (encoder inputs A, B, and Z)
Maximum input signal
frequency
100 kHz for pulse/direction counter mode
100 kHz for up/down counter mode
50 kHz for phase differential counter mode (
×
1,
×
2, or
×
4)
Item
Specification
Input type
PNP
Number of inputs
1
ON voltage
15.0 VDC min. (between input terminal and G terminal)
ON current
3.0 mA min.
OFF voltage
5.0 VDC max. (between input terminal and G terminal)
OFF current
1.0 mA max.
ON response time
1 ms max. (See note.)
OFF response time
1 ms max. (See note.)
Item
Specification
Output type
PNP
Number of outputs
2
Total output current
500mA max.
Residual voltage
1.2 V max.
Leakage current
0.1 mA max.
ON response time
1 ms max. (See note.)
OFF response time
1 ms max. (See note.)
Output short-circuit protection
None
Off-wire detection
None
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...