172
Temperature Input Units
Section 6-4
Note
The ERR indicator will not light or flash if input error detection has
been disabled (i.e., if the input error detection disable setting has
been set to disable detection).
An input error occurs when the input value exceeds the convertible tempera-
ture range. Disconnections and cold junction compensation errors are treated
as input errors. Refer to
Convertible Temperature Ranges
on page 175 for
more information. For information on LED indicator troubleshooting, refer to
9-2 LED Indicators and Error Processing
for details.
Setting the Input Type
The input type can be set using the DIP switch or the Setting Tool.
Setting with the DIP
Switch
Each pin is set according to the following table.
Note
If the settings are incorrect, the TS Indicator will flash red and the Unit will not
operate. In this case, make the settings again and turn the power supply OFF
and ON.
ERR1
Red
Lit
Error
An input error has occurred in
input 1.
An error has occurred in the cold
junction compensator
(GRT1-TS2T only).
---
Not lit
Normal status
There is no input error for input 1.
Name
Color
Status
Meaning
Pin
Setting
Specifications
1
Select the input type (i.e., input
range). Make the input type setting
using the combinations in the fol-
lowing table.
Default setting: OFF
2
3
Select a
°
C or
°
F display.
OFF:
°
C conversion
ON:
°
F conversion
Both inputs are set together and cannot be
set individually. The default setting is OFF.
The selection of
°
C or
°
F display cannot be
set with the Setting Tool.
4
Select the input type setting
method. Select either setting with
DIP switch or with the Setting Tool.
OFF: Set with the Setting Tool.
ON: Set with DIP switch.
When the input type is set with the DIP
switch, all inputs must be set to the same
input type. To set different input types, use
the Setting Tool to make the settings.
Default setting: OFF
1
2
3
4
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...