148
Analog Output Units
Section 5-5
User Adjustment
Depending on factors such as the characteristics and connection methods of
the output device, the output can be adjusted to compensate for error in the
final output. The following diagram shows when compensation is applied to
the conversion line at the two points for 0% and 100%.
The ranges supported for adjustment (–5% to +5%) are shown in the following
table. If adjustment cannot be performed within the following ranges, check
the method being used to connect the output device.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1.
In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select
Parameters - Edit
. The Edit Device Parameters
Window will be displayed.
2.
Click the
I/O Module
Tab.
3.
Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
Output range
Low Limit
High Limit
0 to 5 V
–0.25 to 0.25 V
4.75 to 5.25 V
1 to 5 V
0.8 to 1.2 V
4.8 to 5.2 V
0 to 10 V
–0.5 to 0.5 V
9.5 to 10.5 V
–10 to 10 V
–11 to –9.0 V
9.0 to 11 V
4 to 20 mA
3.2 to 4.8 mA
19.2 to 20.8 mA
0 to 20 mA
0.2 to 1.0 mA
19 to 21 mA
100%
0%
Conversion data
After adjustment
Before adjustment
Voltage/current
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...