192
Temperature Input Units
Section 6-4
■
Example of Bottom Hold
Note
A delay in network transmission time will occur from the time the Hold Flag
turns ON (or OFF) in the Master’s ladder program until notification of the flag’s
status is actually sent to the Slave. Therefore, even when the Hold Flag is ON,
the first temperature data transmitted to the Master when the CPU Unit power
is turned ON may be the data from when the Hold Flag was OFF. To collect
peak/bottom hold data using the Hold Flag at the Master, configure a ladder
program that considers the transmission delay when the Hold Flag is turned
ON, then enables the peak/bottom hold values after a fixed time interval.
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1.
In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select
Pa-
rameters - Edit
. The Edit Unit Parameters Window will be displayed.
2.
Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3.
Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4.
Select the tab page for the input where peak/bottom hold is to be set, and
select the
Peak/Bottom Hold
Check Box in the
Function Choice
Area.
ON
OFF
Temperature input value
The bottom value
will be updated.
Hold value
Previous value
Hold Flag
Bottom hold value
Hold function starts
Hold function stops
Summary of Contents for SmartSlice GRT1-Series
Page 1: ...Slice I O Units Cat No W455 E1 06 SmartSlice GRT1 Series OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised November 2007 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 21: ...xxii EC Directives 6 ...
Page 63: ...42 Connecting Turnback Cables Section 3 3 ...
Page 109: ...88 Digital I O Units Section 4 6 ...
Page 251: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Page 293: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Page 301: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Page 323: ...302 Troubleshooting by Unit Section 9 5 ...
Page 351: ...330 Explicit Messages Appendix A ...
Page 355: ...334 Power Consumption and Weight Tables Appendix C ...
Page 357: ...336 I O Current Consumption Table Appendix D ...
Page 365: ...344 Revision History ...