5
SAFETY I/O interf
ace
5-3
1.4 Connections example of dedicated input signal
1.4.1
Emergency stop inputs (E-STOP RDY*, E-STOP COM*)
E-STOP RDY1
3.3k
Ω
7 mA
DC24V
E-STOP COM1
E-STOP RDY2
3.3k
Ω
7 mA
E-STOP COM1
L
N
45 mA
45 mA
To main power circuit
Main power on/off control
The emergency stop inputs are used to construct a physical emergency stop circuit as a safety protection
function of the overall system including the controller.
To operate the robot, the emergency stop input contact needs to be closed.
When the emergency stop input contact is closed (ON), the servo power can be turned on. When any
emergency stop input contact is open (OFF), the servo power cannot be turned on.
To drive the internal power relay that is connected in parallel, E-STOP RDY*/E-STOP COM* needs 45-mA
current.
1.4.2
AUTO mode inputs (AUTO*+, AUTO COM*)
AUTO1+
3.3k
Ω
7 mA
DC24V
AUTO COM1
AUTO2+
3.3k
Ω
7 mA
AUTO COM2
The AUTO mode inputs are valid only for the controller with the CE specifications.
They can change the external safety circuit of the controller to the AUTO mode and inform that the robot is in
the automatic operation ready status. When either AUTO mode input turns off, the controller changes to the
MANUAL mode. For the controller with the standard specifications, the operation mode can be changed only
from the manual lock switch on the programming box.
Summary of Contents for R6YXC1000
Page 1: ...7 6HULHV DW 1R 1 5 5RERW RQWUROOHU 86 5 6 0 18 6 5 5RERWV 5 6HULHV...
Page 2: ......
Page 10: ......
Page 40: ......
Page 42: ......
Page 46: ......
Page 48: ......
Page 54: ......
Page 56: ......
Page 64: ......
Page 80: ......
Page 82: ......
Page 102: ......
Page 108: ......
Page 110: ......
Page 136: ......
Page 168: ......
Page 170: ......
Page 174: ...8 Periodic inspection 8 4...
Page 176: ......
Page 182: ......
Page 256: ......
Page 258: ......
Page 259: ......
Page 260: ...DW 1R 1 XWKRUL HG LVWULEXWRU 3ULQWHG LQ XURSH...