![Omron NC1-510000 User Manual Download Page 111](http://html1.mh-extra.com/html/omron/nc1-510000/nc1-510000_user-manual_742744111.webp)
Hardware Arrangement
The coils and contacts in electromagnetic contacts and relays in an external circuit are sources of
noise. Do not install them close to the AMR Controller. Locate them at least 100 mm away from the
AMR Controller.
Example of Arrangement in Panel
AC I/O
device
Terminal block
DC I/O
device
OMRON
product
Wire Layout for the Power Supply
Observe the following points when wiring the power supply system.
• Separate the AMR Controller power supply from the I/O device power supply and install a noise filter
near the AMR Controller power supply feed section.
• Use an isolating transformer to significantly reduce noise between the AMR Controller and the
ground. Install the isolating transformer between the AMR Controller power supply and the noise fil-
ter, and do not ground the secondary coil of the transformer.
• Keep the wiring between the transformer and the AMR Controller as short as possible, twist the
wires well, and keep the wiring separate from high-voltage and power lines.
Unit power supply for Omron product
I/O power supply for Omron product
Power Supply System Diagram
Power circuits
Power supply for general operations circuits
Outlet (for peripheral devices)
I/O power supply for Omron product
Noise
filter
5 Installation
5-13
AMR Controller User's Guide (I650)
5-3 Mount
5
5-3-7
Electrical Environment
Summary of Contents for NC1-510000
Page 1: ...AMR Controller User s Guide NC1 510000 NC1 510001 AMR Controller I650 E 01...
Page 4: ...Introduction 2 AMR Controller User s Guide I650...
Page 36: ...1 Overview 1 6 AMR Controller User s Guide I650...
Page 156: ...7 Maintenance 7 8 AMR Controller User s Guide I650...
Page 183: ...I Index I 1 AMR Controller User s Guide I650 I...
Page 186: ...Index I 4 AMR Controller User s Guide I650...
Page 187: ......