1178h
Light load signal output
mode
C038
R/W
00: Enabled during acceleration/
deceleration/constant speed
01: Enabled only during constant speed
⎯
1179h
Light load detection level
C039
R/W
0 to 20000
Set to10000 at rated current
0.01 [%]
1124h
Overload warning level
C041
R/W
0 to 20000
Set to10000 at rated current
0.01 [%]
153Ah
2nd overload warning level
C241
R/W
1126h
Arrival frequency during
acceleration
C042
R/W
0 to 4000
0.1 [Hz]
1128h
Arrival frequency during
deceleration
C043
R/W
0 to 4000
0.1 [Hz]
1129h
PID deviation excessive
level
C044
R/W
0 to 1000
0.1 [%]
112Eh
PID FB upper limit
C052
R/W
0 to 1000
0.1 [%]
112Fh
PID FB lower limit
C053
R/W
0 to 1000
0.1 [%]
1137h
Operator/ModBus selection
C070
⎯
Do not change through ModBus
communication. For setting, refer to
"ModBus Setting" (4-65).
⎯
1138h
Communication speed
selection
(Baud rate selection)
C071
⎯
1139h
Communication station No.
selection
C072
⎯
113Bh
Communication parity
selection
C074
⎯
113Ch
Communication stop bit
selection
C075
⎯
113Dh
Communication error
selection
C076
⎯
113Eh
Communication error
timeout
C077
⎯
113Fh
Communication wait time
C078
⎯
1141h
O adjustment
C081
R/W
0 to 2000
0.1 [%]
1142h
OI adjustment
C082
R/W
0 to 2000
0.1 [%]
1145h
AM offset adjustment
C086
R/W
0 to 100
0.1 [V]
⎯
Not used
C091
⎯
Do not change.
⎯
1149h
UP/DWN selection
C101
R/W
00: OFF/01: ON
⎯
114Ah
Reset selection
C102
R/W
00: Trip reset at power-on
01: Trip reset when the power is OFF
02: Enabled only during trip (Reset when
the power is ON.)
⎯
1150h
Logic operation function A
input
C141
R/W
00: RUN/01: FA1/02: FA2/03: OL/04:
OD/05: AL/06: Dc/07: FBV/08: NDc/10:
ODc(Do not use.)/43: LOC
⎯
1151h
Logic operation function B
input
C142
R/W
1152h
Logic operator selection
C143
R/W
00: AND/01: OR/02: XOR
⎯
1153h
Output terminal 11 ON delay
C144
R/W
0 to 1000
0.1 [s]
1154h
Output terminal 11 OFF
delay
C145
R/W
0 to 1000
1157h
Relay output ON delay
C148
R/W
0 to 1000
1158h
Relay output OFF delay
C149
R/W
0 to 1000
Register
No.
Function name
Parameter
No.
R/W
Function
Monitor or data range
Resolution
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......