7
Safety Precautions
“Suitable for use on a circuit capable of delivering not more than 100k rms symmetrical amperes,
480V maximum when protected by Class CC, G, J or R fuses or circuit having an interrupting rating
not less than 100,000 rms symmetrical amperes, 480 volts maximum”. For the 400V models
“Install device in pollution degree 2 environment”.
“Maximum Surrounding Air Temperature 50
°
C
” or equivalent
“Caution-Risk of electric shock-capacitor discharge time is at least 5 minutes.”
“Solid state motor overload protection is provided in each model”.
“Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electric Cod3e and any additional
local codes” or equivalent.