3-6
3-2 Test Run Operation
3
Operation
Setting the Motor Capacity Selection (H003) and Motor Pole Number Selection
(H004)
Parameter
No.
Register
No.
Name
Description
Setting range
Unit of
setting
Default
setting
Change
during
RUN
H003
1165h
Motor capacity
selection
Sets the capacity of the
motor connected to the
Inverter.
200-V class
0.2/0.4/0.75/
1.5/2.2/3.7/
5.5/7.5
400-V class
0.4/0.75/1.5/
2.2/3.7/5.5/7.5
kW
Varies with
the
capacity.
No
H004
1166h
Motor pole
number
selection
Sets the pole number of the
motor connected to the
Inverter.
2/4/6/8
Pole
4
No
Key sequence
Display example
Description
Press the Mode key twice to display the mode selection.
Use the Increment or Decrement key to display "H---".
Press the Mode key. "H003" is displayed.
Press the Mode key. The set value in "H003" is displayed.
Use the Increment or Decrement key to set the rated motor capacity.
Press the Enter key. The set value is entered.
(In approx. 1 s)
The parameter number is displayed again.
b---
h---
h003
0.20
0.40
0.40
h003
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......