2-23
2-2 Wiring
2
De
sign
*4. For the external analog input indicated above, use a shielded wire for connection and connect the shielded
part to terminal L for stable operation.
*5. Below are the contact specifications of the relay output.
*6.
By factory default, the relay output (AL2, AL1) contact selection (C036) is set at NC contact between AL2-AL0, and
NO contact between AL1-AL0.
Mode Selector
RS-485 Communication/Operator Selector (S7)
Select the mode according to the option connected to the communications connector.
When using the 3G3AX-OP01 supplied with the Inverter, it is available regardless of the switch
condition.
Emergency shutoff selector (S8)
Use this selector to enable the emergency shutoff input function.
*1 The multi-function input terminal 3 is switched to a terminal for emergency shutoff input, and the allocation of
other multi-function input terminals is also changed automatically. Do not set to ON immoderately. For details,
refer to "Emergency Shutoff Input Function" (page 4-46).
Output
terminal
Contact
capacity
Resistance load
Inductive load
AL2-AL0
Max.
250 V AC 2.5 A
30V DC 3 A
250 V AC 0.2 A
30 V DC 0.7 A
Min.
100 V AC 10 mA
5 V DC 100 mA
AL1-AL0
Max.
250 V AC 1 A
30 V DC 1 A
250 V AC 0.2 A
30 V DC 0.2 A
Min.
100 V AC 10 mA
5 V DC 100 mA
Inside the Inverter
(Factory default)
AL1 AL2 AL0
Symbol
Name
Status
Description
S7
RS-485 communication/
operator selector
485
RS485 ModBus communication
OPE [Default]
Digital Operator (Option: 3G3AX-OP1)
Symbol
Name
Status
Description
S8
Emergency
shutoff
selector
ON
Emergency shutoff input enabled
*1
OFF
[Default]
Normal
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......