4-20
4-2 Function Mode
4
Func
tions
•When the reference frequency reaches 2 Hz or higher than the set value in A052, DC injection
braking is released and the output returns to normal. (Example 6-a)
•If the reference frequency is "0" when the operation starts with analog input, the initial operation is
DC injection braking because both the reference and current frequencies are "0". (Example 6-b)
•If the RUN command is turned on with the frequency reference established (or a value larger than
the A052 setting is input), the initial operation is normal output.
•The operation to return to normal varies depending on the setting of the DC injection braking
method selection (A056).
.Frequency Limit
This function limits the Inverter output frequency.
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
(Example 6-a)
(Example 6-b)
ON
RUN
command
A052
Frequency
reference
Output
frequency
ON
RUN
command
A052
Frequency
reference
Output
frequency
(a) Edge operation
(b) Level operation
ON
RUN
command
A052
Frequency
reference
Output
frequency
A053
ON
RUN
command
A052
Frequency
reference
Output
frequency
Parameter No.
Function name
Data
Default setting
Unit
A061
Frequency upper limit
0.0/Frequency lower limit [A062] to
Max. frequency [A004]
0.0
Hz
*
A261
2nd frequency upper
limit
0.0/Frequency lower limit [A262] to
Max. frequency [A204]
0.0
A062
Frequency lower limit
0.0/Starting frequency to Frequency
upper limit [A061]
0.0
*
A262
2nd frequency lower
limit
0.0/Starting frequency to Frequency
upper limit [A261]
0.0
Related parameters
C001 to C005
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......