![background image](http://html.mh-extra.com/html/omron/jx-a4004/jx-a4004_user-manual_742715185.webp)
7-3
7-1 Standard Specification List
7
Specifications
1-phase 200-V Class
*1. The applicable motor is a 3-phase standard motor. For using any other type, be sure that the rated current
does not exceed that of the Inverter.
*2. Output voltage decreases according to the level of the power supply voltage.
*3. The braking torque at the time of capacitor feedback is an average deceleration torque at the shortest
deceleration (when it stops from 50 Hz), not a continuous regenerative torque. Also, the average deceleration
torque varies depending on the motor loss. The value is reduced in operation at over 50 Hz. Note that no
regenerative braking circuit is built into the Inverter. If you need a larger regenerative torque, use the
optionally available regenerative braking unit and resistor. The regenerative braking unit should be used only
for short-time regeneration.
Item
1-phase 200-V class
Model name (JX-)
AB002
AB004
AB007
AB015
AB022
Applicable motor
capacity
*1
kW
0.2
0.4
0.75
1.5
2.2
HP
1/4
1/2
1
2
3
Rated output capacity
(kVA)
200 V
0.4
0.9
1.3
2.4
3.4
240 V
0.5
1.0
1.6
2.9
4.1
Rated input voltage
1-phase 200 V -15% to 240 V +10% 50/60 Hz ±5%
Built-in filter
EMC FILTER (EN61800-3 category C1)
Model without Built-in EMC filter is also available
Rated input current (A)
1.8
3.4
5.2
9.3
13.0
Rated output voltage
*2
3-phase: 200 to 240 V (Proportional to input voltage)
Rated output current (A)
1.4
2.6
4.0
7.1
10.0
Weight [kg]
0.8
0.9
1.5
2.3
2.4
Cooling method
Self-cooling
Forced-air-cooling
Braking
torque
At short-time
deceleration
*3
At capacitor feedback
Approx. 50%
Approx. 20% to 40%
DC injection braking
Injection braking frequency/time, braking force variable,
frequency control available
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......