4-2 Function Mode
4
Functions
Parameter Initialization
You can initialize the rewritten set values and reset to the factory default, or clear trip records.
Note that this is not available for RUN and power ON times.
The multi-function input/output terminals are also initialized with this function. To avoid unexpected
operation, be sure to re-examine the wiring.
Refer to page 3-5 for more details about the initialization process.
Frequency Conversion Coefficient
This function displays a conversion value obtained by multiplying the Inverter output frequency by
the coefficient set in [b086]. This helps display the actual physical value on the monitor.
Displayed value [d007] = "Output frequency [d001]" x "Frequency conversion coefficient [b086]"
Refer to page
4-3
for more details
STOP Key Selection
You can select whether to enable the STOP key on the Digital Operator, even if the RUN command
is set to the control terminal block (terminal).
•The trip reset function via the STOP/RESET key works according to this setting.
Free-run Stop
This function sets the motor to free running status by shutting off the Inverter output. Also You can
select the operation to be performed when the free-run stop input is reset, and select the stop meth-
od, deceleration stop or free-run stop.
Parameter No.
Function name
Data
Default setting
Unit
b084
Initialization selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes
data
00
⎯
b085
Initialization parameter
selection
00: Do not change.
00
⎯
Parameter No.
Function name
Data
Default setting
Unit
b086
Frequency conversion
coefficient
0.1 to 99.9
1.0
⎯
Related parameters
d007
Parameter No.
Function name
Data
Default setting
Unit
b087
STOP key selection
00: Enabled
01: Disabled
00
⎯
Parameter No.
Function name
Data
Default setting
Unit
b088
Free-run stop selection
00: 0 Hz start
01: Active Frequency Matching
restart
00
⎯
b091
Stop selection
00: Deceleration
→
Stop
01: Free-run stop
00
⎯
b003
Retry wait time
0.3 to 100.
1.0
s
Related parameters
C001 to C005, b003
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......