4-47
4-2 Function Mode
4
Functions
Inputting EMR to the digital input lets the motor go into "Emergency Shutoff" status (or free-run
status).
This status continues while EMR is turned on or until a reset signal is input.
To use the Inverter to control the mechanical brake (used for cranes, etc.), you need to connect the
safety output of the external safety relay to the brake control circuit in series.
Note 1: For the signal lines for the safety relay and emergency shutoff input, use shielded coaxial
cables with 2.8 mm or less in diameter and 2 m or less in length. The shield must be
grounded.
Note 2: All inductor parts such as the relay and contactor must have overvoltage protection circuits.
With DIP switch S8 turned on, multi-function input 3 is automatically allocated to the emergency
shutoff signal EMR input terminal, and 4 to the reset signal input terminal. In this case, EMR is
allocated to function code C003, and reset (RS) to C004 automatically, and you cannot change
these parameters manually. The following table shows the status of DIP switch S8 and the
allocation of the multi-function input.
In short, when DIP switch S8 is turned on, input terminal 5 automatically switches to "No function
allocated" status. To allocate a function to terminal 5 in this status, use the function mode.
If DIP switch S8 is turned off later, input terminal 3 switches to "No function allocated" status. To
allocate a function, again use the function mode.
You can reset Emergency Shutoff status only via the dedicated input terminal (terminal 4 in the
above table). The STOP/RESET button on the Digital Operator cannot be used for resetting
Emergency Shutoff status.
* When DIP switch S8 is ON, the EMR function is forcibly set to NC contact, and the RS function to
NO contact.(Parameters C013 and C014 are ignored)
2nd Control Function and Special 2nd Function
This function is used to operate by switching two different types of motors or additional parameter
sets
Multi-function input
terminal No.
Emergency shutoff selector S8
S8 = OFF
(Default)
S8 = OFF
→
ON
S8 = ON
→
OFF
Status
1
2
3
1
FW
FW
FW
2
RV
RV
RV
3
CF1
EMR *
(only for emergency
shutoff)
No function allocated
4
CF2
RS *
(only for emergency
shutoff reset)
RS
(normal reset)
5
(also used for PTC)
RS
No function allocated
No function allocated
Data
Symbol
Function name
Status
Description
08
SET
2nd control
ON
Enables the parameter for the 2nd motor.
OFF
Disables the parameter for the 2nd motor.
53
SP-SET
Special 2nd function
ON
Enables the parameter for the special 2nd motor.
OFF
Disables the parameter for the special 2nd motor.
Related parameters
C001 to C005
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......