4-84
4-2 Function Mode
4
Func
tions
10A5h
Retry selection
b001
R/W
00: Alarm
01: 0 Hz start
02: Frequency matching restart
03: Trip after frequency matching
deceleration stop
⎯
10A6h
Allowable momentary power
interruption time
b002
R/W
3 to 250
0.1 [s]
10A7h
Retry wait time
b003
R/W
3 to 1000
0.1 [s]
10A8h
Momentary power
interruption/undervoltage
trip during stop selection
b004
R/W
00: Disabled
01: Enabled
⎯
10A9h
Momentary power
interruption retry time
selection
b005
R/W
00: 16 times
01: No limit
⎯
1170h
Starting frequency at Active
Frequency Matching restart
b011
R/W
00: Frequency at interruption
01: Max. frequency
02: Set frequency
⎯
10ADh
Electronic thermal level
b012
R/W
2000 to 10000
Set the rated current to 10000
0.01 [%]
1527h
2nd electronic thermal level
b212
R/W
10AEh
Electronic thermal
characteristics selection
b013
R/W
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
⎯
1528h
2nd electronic thermal
characteristics selection
b213
R/W
⎯
10B5h
Overload limit selection
b021
R/W
00: Disabled
01: Enabled in acceleration/constant
speed operation
02: Enabled in constant speed operation
⎯
1529h
2nd overload limit selection
b221
R/W
⎯
10B6h
Overload limit level
b022
R/W
2000 to 15000
Set the rated current to 10000
0.01 [%]
152Ah
2nd overload limit level
b222
R/W
10B7h
Overload limit parameter
b023
R/W
1 to 300
0.1 [s]
152Bh
2nd overload limit parameter
b223
R/W
10BBh
Overload limit source
selection
b028
R/W
00: Set values in b022
01: Input O terminal
⎯
152Ch
2nd overload limit source
selection
b228
R/W
00: Set values in b222
01: Input O terminal
⎯
1171h
Deceleration rate constant at
Active Frequency Matching
restart
b029
R/W
1 to 30000
0.1 [s]
1172h
Active Frequency Matching
restart level
b030
R/W
200 to 20000
0.01 [%]
10BCh
Soft lock selection
b031
R/W
00: Data other than b031 cannot be
changed when terminal SFT is ON.
01: Data other than b031 and the
specified frequency parameter
cannot be changed when terminal
SFT is ON.
02: Data other than b031 cannot be
changed.
03: Data other than b031 and the
specified frequency parameter
cannot be changed.
10: Data other than parameters
changeable during operation cannot
be changed.
⎯
Register
No.
Function name
Parameter
No.
R/W
Function
Monitor or data range
Resolution
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......