4-85
4-2 Function Mode
4
Functions
10C9h
Selection of non-stop
function at momentary
power interruption
b050
R/W
00: Disabled
01: Enabled (Stop)
02: Enabled (Restart)
⎯
10CAh
Starting voltage of non-stop
function at momentary
power interruption
b051
R/W
0 to 10000
0.1 [V]
10CBh
Stop deceleration level of
non-stop function at
momentary power
interruption
b052
R/W
0 to 10000
0.1 [V]
10CCh
Deceleration time of non-
stop function at momentary
power interruption
b053
R/W
1 to 30000
0.1 [s]
10CEh
Deceleration starting width
of non-stop function at
momentary power
interruption
b054
R/W
0 to 100
0.1 [Hz]
1173h
Overvoltage protection
proportional gain during
deceleration
b055
R/W
2 to 50
0.1
1174h
Overvoltage protection
integral time during
deceleration
b056
R/W
0 to 1500
0.1 [s]
10CFh
AM adjustment
b080
R/W
0 to 255
⎯
10D1h
Starting frequency
b082
R/W
5 to 99
0.1 [Hz]
10D2h
Carrier frequency
b083
R/W
20 to 120
0.1 [kHz]
10D3h
Initialization selection
b084
R/W
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes
data
⎯
10D4h
Initialization parameter
selection
b085
R/W
00: Fixed
*Do not change.
⎯
10D5h
Frequency conversion
coefficient
b086
R/W
1 to 999
0.1
10D6h
STOP key selection
b087
R/W
00: Enabled
01: Disabled
⎯
10D7h
Free-run stop selection
b088
R/W
00: 0 Hz start
01: Active Frequency Matching restart
⎯
10D8h
Monitor display selection
b089
R/W
01: Output frequency monitor
02: Output current monitor
03: Rotation direction monitor
04: PID feedback value monitor
05: Multi-function input monitor
06: Multi-function output monitor
07: Frequency conversion monitor
⎯
10DAh
Stop selection
b091
R/W
00: Deceleration
→
Stop
01: Free-run stop
⎯
10DBh
Cooling fan control
b092
R/W
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
⎯
10F5h
Overvoltage LAD stop
function
b130
R/W
00: Disabled
01: Enabled
⎯
10F6h
Overvoltage LAD stop
function level setting
b131
R/W
200-V class: 330 to 395,
400-V class: 660 to 790
1. [V]
Register
No.
Function name
Parameter
No.
R/W
Function
Monitor or data range
Resolution
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...
Page 217: ...INDEX ...
Page 220: ......