2-2 Wiring
2
De
sign
Explanation of the Main Circuit Terminal Connection
* For
JX-AB
's terminal symbols, R/L1 corresponds to L1, S/L2 to L2, and T/L3 to N/L3.
Connect a single-phase 200-V AC input to terminals L1 and N.
Model
(JX-)
A2002 to A2007
AB002 to AB004
A2015 to A2037
A4004 to A4040
AB007 to AB022
A2055 to A2075
A4055 to A4075
Screw size
W (mm)
Screw size
W (mm)
Screw size
W (mm)
Main circuit
M3.5
7.1
M4
9.2
M5
13
Control circuit
M2
⎯
M2
⎯
M2
⎯
Relay
M2.5
⎯
M2.5
⎯
M2.5
⎯
Ground
M4
⎯
M4
⎯
M5
13
Screw Tightening Torque
Screw
Tightening torque
M2
0.2 N•m (max. 0.25 N•m)
M2.5
0.5 N•m (max. 0.6N•m)
M3.5
0.8 N•m (max. 0.9 N•m)
M4
1.2 N•m (max. 1.3 N•m)
M5
3.0 N•m (max. 3.3 N•m)
Terminal
symbol
Terminal name
Function
Connection example
R/L1, S/L2,
T/L3 *
Main power supply
input terminal
Connect the input power supply.
Do not remove the short-circuit bar
between PD/+1 and P/+ when a DC
reactor is not connected.
U/T1,
V/T2, W/T3
Inverter output
terminal
Connect to the motor.
PD/+1,
P/+
External DC reactor
terminal
Normally connected by the short-circuit
bar. Remove the short-circuit bar
between PD/+1 and P/+ when a DC
reactor is connected.
P/+, N/-
Regenerative
braking unit
connection terminal
Connect optional regenerative braking
units.
Ground terminal
Ground (Connect to ground to prevent
electric shock and reduce noise.)
Power supply
ELB
Motor
Summary of Contents for JX-A4004
Page 2: ......
Page 16: ...14 About This Manual ...
Page 19: ...Chapter 1 Overview 1 1 Functions 1 2 1 2 Appearance and Names of Parts 1 4 ...
Page 24: ......
Page 25: ...Chapter 2 Design 2 1 Installation 2 2 2 2 Wiring 2 7 ...
Page 79: ...Chapter 4 Functions 4 1 Monitor Mode 4 2 4 2 Function Mode 4 6 ...
Page 174: ...5 8 5 2 Troubleshooting 5 Maintenance Operations ...
Page 175: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 2 6 2 Storage 6 8 ...
Page 199: ...Appendix Appendix 1Parameter ListApp 2 Appendix 2Product Life CurveApp 18 ...